Question
Download Solution PDFTo operate two alternators in parallel, which of their quantities must be same?
This question was previously asked in
MPPGCL JE Electrical 19 March 2019 Shift 2 Official Paper
Answer (Detailed Solution Below)
Option 3 : Phase sequence
Free Tests
View all Free tests >
MPPGCL JE Electrical Full Test 1
3.9 K Users
100 Questions
100 Marks
120 Mins
Detailed Solution
Download Solution PDFThe correct answer is option 3.
Reasons for Parallel Operation of Alternators
- Several alternators can supply a bigger load than a single alternator.
- One or more alternators may shut down during the period of light loads. Thus, the remaining alternator operates at near or full load with greater efficiency.
- When one machine is taken out of service for its scheduled maintenance and inspection, the remaining machines maintain the continuity of the supply.
- If there is a breakdown of the generator, there is no interruption of the power supply.
Necessary Conditions for Paralleling Alternators
- The phase sequence of the busbar voltages and the incoming alternator voltage must be the same.
- The phase angle of the two systems must be equal.
- The busbar voltages and the terminal voltage of the incoming alternator must be in phase.
- The frequency of the generated voltage of the incoming machine must be equal to the frequency of the voltages of the busbar.
- The terminal voltage of the incoming alternator must be equal to the busbar voltages.
Last updated on May 29, 2025
-> MPPGCL Junior Engineer result PDF has been released at the offiical website.
-> The MPPGCL Junior Engineer Exam Date has been announced.
-> The MPPGCL Junior Engineer Notification was released for 284 vacancies.
-> Candidates can apply online from 23rd December 2024 to 24th January 2025.
-> The selection process includes a Computer Based Test and Document Verification.
-> Candidates can check the MPPGCL JE Previous Year Papers which helps to understand the difficulty level of the exam.