Question
Download Solution PDFTwo 25 MVA, 3 phase alternators operate in parallel to supply a load of 35 MVA at 0.8 power factor lagging. If the output of one machine is 25 MVA at 0.8 lagging, what is the output and power factor of the other machine?
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFCalculation: Given,
Rating of Generators = 25 MVA
Rating of load = 35 MVA at 0.8 p.f lagging
= 35 MVA ∠-36.86°
If two generators are connected in parallel then both will combinedly supply the load demand.
i.e, S1 + S2 = SL
∴ S1 = 25 ∠-36.86°
SL = 35 ∠-36.86°
∴ S2 = SL - S1
= 35 ∠-36.86 - 25 ∠-36.86°
= 10 ∠-36.86°
= 10 MVA, 0.8 p.f lagging
Note:- Here '-ve' sign indicates p.f as lagging.
Therefore, option (2) is correct.