Protective Relays MCQ Quiz - Objective Question with Answer for Protective Relays - Download Free PDF

Last updated on May 30, 2025

Latest Protective Relays MCQ Objective Questions

Protective Relays Question 1:

Which of the following characteristics is associated with a distance relay used for fault protection?

  1. It operates based on the impedance between the relay and the fault.
  2. It is used only for short-circuit protection.
  3. It operates based on the current only.
  4. It operates based on the voltage at the fault location.

Answer (Detailed Solution Below)

Option 1 : It operates based on the impedance between the relay and the fault.

Protective Relays Question 1 Detailed Solution

Explanation:

Distance Relay for Fault Protection

Definition: A distance relay is a type of protective relay used in power systems to detect and isolate faults. It operates based on the impedance between the relay location and the fault location. The primary function of a distance relay is to protect transmission lines from faults by measuring the impedance, which is inversely proportional to the distance to the fault.

Distance relays measure the voltage and current at the relay location and calculate the impedance (Z = V/I). When a fault occurs, the impedance changes significantly. If the calculated impedance falls within a predetermined zone, the relay identifies the presence of a fault and triggers the protection mechanism to isolate the faulty section.

Correct Option Analysis:

The correct option is:

Option 1: It operates based on the impedance between the relay and the fault.

This option correctly describes the functioning of a distance relay. The relay measures the impedance between its location and the fault, and if the impedance falls within a predetermined range, it indicates a fault condition and initiates the protection mechanism.

Additional Information

To further understand the analysis, let’s evaluate the other options:

Option 2: It is used only for short-circuit protection.

This option is incorrect because distance relays are used for various types of fault protection, not just short-circuit protection. They can detect phase-to-phase faults, phase-to-ground faults, and other abnormal conditions on the transmission line.

Option 3: It operates based on the current only.

This option is incorrect because a distance relay operates based on both voltage and current measurements to calculate the impedance. Relying on current alone would not provide the necessary information to determine the distance to the fault accurately.

Option 4: It operates based on the voltage at the fault location.

This option is incorrect because, although voltage measurement is part of the relay's operation, the primary basis for its operation is the impedance calculation, which involves both voltage and current. Voltage alone cannot determine the distance to the fault.

Protective Relays Question 2:

Selectivity in a protection relay system refers to:

  1. the ability of the relay to operate only for specific fault types
  2. the ability of the relay to discriminate between fault and normal conditions
  3. the ability of the relay to clear faults without affecting the rest of the system
  4. the ability of the relay to operate with a minimal time delay for all fault conditions

Answer (Detailed Solution Below)

Option 3 : the ability of the relay to clear faults without affecting the rest of the system

Protective Relays Question 2 Detailed Solution

The correct answer is 3) the ability of the relay to clear faults without affecting the rest of the system.

Here's why:

  • Selectivity in a protection relay system ensures that only the circuit element directly affected by a fault is isolated, while the rest of the healthy system continues to operate normally. This means the relay should "select" the faulty section and initiate tripping of the appropriate circuit breaker(s) to isolate it.  

Let's look at why the other options are not the primary definition of selectivity:

  • 1) the ability of the relay to operate only for specific fault types: This describes the sensitivity or characteristic of the relay to respond to certain types of faults (e.g., overcurrent, undervoltage, earth fault). While related to proper operation, it's not the core meaning of selectivity.
  • 2) the ability of the relay to discriminate between fault and normal conditions: This describes the fundamental reliability and security of the relay to distinguish abnormal fault conditions from normal operating conditions or transient disturbances. It's a prerequisite for any protection system, but not specifically selectivity.
  • 4) the ability of the relay to operate with a minimal time delay for all fault conditions: This describes the speed of operation of the relay. While fast fault clearing is desirable, selectivity might sometimes involve intentional time delays in coordination with other relays to ensure the correct sequence of tripping and isolation of the faulty section.

Protective Relays Question 3:

What is the primary function of a voltage differential relay in an electrical protection system?

  1. It detects phase angle differences between the currents and trips the system if the angle exceeds a set limit.
  2. It measures the impedance across the circuit and operates when a fault is detected.
  3. It compares the current entering and leaving the protected zone to detect faults.
  4. It detects the difference in voltage between two or more points and trips the system if the voltage difference exceeds a set threshold.

Answer (Detailed Solution Below)

Option 4 : It detects the difference in voltage between two or more points and trips the system if the voltage difference exceeds a set threshold.

Protective Relays Question 3 Detailed Solution

The correct answer is: 4) It detects the difference in voltage between two or more points and trips the system if the voltage difference exceeds a set threshold.

Explanation:
The primary function of a voltage differential relay is to:

  • Compare voltages at two or more points in the system (e.g., across a transformer winding, busbar, or transmission line).
  • Detect imbalances (differences) in these voltages.
  • Trip the circuit breaker if the voltage difference exceeds a predefined threshold, indicating a fault (e.g., short circuit, open circuit, or insulation failure).


Option Analysis
Phase angle differences in currents → This describes a phase comparison relay, not a voltage differential relay.

Impedance measurement → This is the function of an impedance relay (used in distance protection).

Current entering/leaving a zone → This describes a current differential relay, which operates based on Kirchhoff’s current law (not voltage).

Thus, the correct choice is 4).

Protective Relays Question 4:

The Time Setting Multiplier (TSM) of a relay is used to:

  1. adjust the operating current threshold of the relay
  2. increase the current setting of the relay
  3. modify the time delay based on fault severity
  4. decrease the time delay of the relay

Answer (Detailed Solution Below)

Option 3 : modify the time delay based on fault severity

Protective Relays Question 4 Detailed Solution

Explanation:

The Time Setting Multiplier (TSM) of a Relay

The Time Setting Multiplier (TSM) is a critical parameter in the operation of protective relays, especially in the context of overcurrent and differential protection schemes. The TSM adjusts the time delay characteristic of the relay, which influences how quickly the relay responds to fault conditions. This adjustment is crucial for coordinating the protection devices within an electrical system to ensure selective tripping and minimize disruption to the power supply.

Analysis of Other Options:

Option 1: Adjust the Operating Current Threshold of the Relay

This option is incorrect because the operating current threshold, also known as the pickup current, is typically adjusted using the current setting parameter of the relay. The TSM is concerned with the time delay characteristics rather than the current threshold.

Option 2: Increase the Current Setting of the Relay

This option is incorrect as well. Increasing the current setting of the relay would mean changing the current level at which the relay starts to operate (pickup level), which is not the function of the TSM. The TSM specifically adjusts the time delay after the relay has picked up a fault current.

Option 4: Decrease the Time Delay of the Relay

While this option is partially correct, it is incomplete. The TSM can indeed decrease the time delay of the relay, but its primary function is to modify the time delay based on fault severity, meaning it can both increase and decrease the time delay as required for proper coordination. Therefore, option 3 is more comprehensive and accurate.

Protective Relays Question 5:

Which of the following best defines the sensitivity of a protective relay?

  1. The ability of the relay to discriminate between different types of faults.
  2. The capacity of the relay to handle high fault currents without damage.
  3. The ability of the relay to detect and respond to very small fault currents.
  4. The time it takes for the relay to react after detecting a fault.

Answer (Detailed Solution Below)

Option 3 : The ability of the relay to detect and respond to very small fault currents.

Protective Relays Question 5 Detailed Solution

The correct answer is: 3) The ability of the relay to detect and respond to very small fault currents.

Explanation:

Sensitivity in protective relays refers to:

  • The minimum fault current (or power, voltage, etc.) that the relay can reliably detect and respond to.

  • A highly sensitive relay can operate for very small fault currents, ensuring protection even for minor faults.

Top Protective Relays MCQ Objective Questions

An over-current relay, having a current setting of 12.5% is connected to a supply circuit through a current transformer with a ratio of 400/5. The pick-up value of the current in Amperes is:

  1. 0.625
  2. 10
  3. 12.5
  4. 15

Answer (Detailed Solution Below)

Option 1 : 0.625

Protective Relays Question 6 Detailed Solution

Download Solution PDF

Concept:

The pick-up current of a relay is given by:

Pick-up current = Rated secondary current of CT × Current setting

Calculation:

Given, the CT ratio = 400/5

Secondary current = 5 A

Relay setting = 12.5%

Pick-up current = 5 × 0.125

Pick-up current = 0.625 A

A negative sequence relay is commonly used to protect

  1. An alternator
  2. A transformer
  3. A transmission line
  4. A bus bar

Answer (Detailed Solution Below)

Option 1 : An alternator

Protective Relays Question 7 Detailed Solution

Download Solution PDF

Negative sequence relay:

  • It protects generators from the unbalanced load by detecting negative sequence current.
  • A negative sequence current may cause a dangerous situation for the machine.
  • Phase to phase fault mainly occurs because of the negative sequence component.
  • The negative sequence relay has earthing which protects from phase-to-earth fault but not from phase-to-phase fault.

Note: 

Relay

Application

Buchholz relay

Transformer

Translay relay

Feeder

Carrier current, phase comparison relay, Mho's relay

Long overhead transmission line

Directional overcurrent relay

Ring main distributor

Negative sequence relay

Generator

Inverse directional overcurrent relay Radial distribution

If for an IDMT relay with a plug setting of 50% and a CT ration of 400/5, the current is 3000 A, then the plug setting multiplier would be:

  1. 7.5
  2. 15.0
  3. 18.75
  4. 37.5

Answer (Detailed Solution Below)

Option 2 : 15.0

Protective Relays Question 8 Detailed Solution

Download Solution PDF

Concept:

Plug setting multiplier:

Plug setting multiplier is the ratio of fault current and the product of plug setting and CT ratio.

Plug setting multiplier \(= \frac{{fault\;current}}{{plug\;setting \times CT\;ratio}}\)

Calculation:

Plug setting = relay setting × secondary CT current

= 0.5 × 5 = 2.5

CT ratio \(= \frac{{400}}{5} = 80\)

Plug setting multiplier \(= \frac{{3000}}{{2.5 \times 80}} = 15\)

A relay is connected to a 400/5 ratio current transformer with circuit setting of 150%. Calculate the plug setting multiplier when circuit carries a fault current of 3000 A.

  1. 5
  2. 6
  3. 8
  4. 7

Answer (Detailed Solution Below)

Option 1 : 5

Protective Relays Question 9 Detailed Solution

Download Solution PDF

Concept:

Plug setting multiplier is the ratio of fault current and the product of plug setting and CT ratio.

Plug setting multiplier \(= \frac{{fault\;current}}{{plug\;setting \times CT\;ratio}}\)

Calculation:

Plug setting = relay setting × secondary CT current

= 1.5 × 5 = 7.5

CT ratio \(= \frac{{400}}{5} = 80\)

Plug setting multiplier \(= \frac{{3000}}{{7.5 \times 80}} = 5\)

Match the items is List – I (Type of transmission line) with the items in List – II (Type of distance relay preferred) and select the correct answer using the codes given below the lists.

    List – 1                                          

a. Short Line                        

b. Medium Line                                 

c. Long Line                                      

  List - II

1. Ohm Relay

2. Reactance Relay     

3. Mho Relay

  1. a → 2, b → 1, c → 3
  2. a → 3, b → 2, c → 1
  3. a → 1, b → 2, c → 3
  4. a → 1, b → 3, c → 2

Answer (Detailed Solution Below)

Option 1 : a → 2, b → 1, c → 3

Protective Relays Question 10 Detailed Solution

Download Solution PDF

Distance Relay:

  • A distance protection relay is a name given to the protection, whose action depends on the distance of the feeding point to the fault.
  • The time of operation of such protection is a function of the ratio of voltage and current, i.e., impedance.
  • This impedance between the relay and the fault depends on the electrical distance between them.
  • Types of distance relays are impedance relays, reactance relays, and the mho relays.

 

Transmission line

Length &  Operating voltage

Distance Relay

Short-line

(0-80) km

(0-20) kV

Reactance relay

Medium line

(80-200) km

(20-100) kV

Ohm relay

Long-line

(>200) km

(>100) kV

Mho relay

 

 

 

 

 

 

 

 

Important Points

  • Reactance relay is suitable for the protection of a short transmission line because its operation is independent of arc resistance.
  • The relay which is selected for a long transmission line should be less affected due to power swings. Hence Mho relay is preferred.
  • Ohm relay is suitable for medium transmission lines.

Impedance relay is used for protection in:

  1. medium transmission lines
  2. short transmission lines
  3. both long transmission lines and short transmission lines
  4. long transmission line

Answer (Detailed Solution Below)

Option 1 : medium transmission lines

Protective Relays Question 11 Detailed Solution

Download Solution PDF

Distance Relay:

This type of relay is used for the protection of the transmission lines.

Depending upon the length of the transmission line, the distance relay is divided into:

1.) Impedance Relay:

  • This relay is a voltage restrained overcurrent relay.
  • This relay operates when the impedance seen from the fault point is less than the relay setting (Z).
  • It is used in the protection of medium transmission lines.

2.) Reactance Relay:

  • This relay is a current restrained overcurrent relay.
  • This relay is used for the protection of short transmission lines.
  • Reactance relay is independent of resistance value.

3.) Mho Relay:

  • This relay is used for the protection of long transmission lines.
  • Mho relay is least affected by power surges.
  • Mho relay is inherently a directional relay as it detects the fault only in the forward direction.

Shortcut Trick

R Short
I Medium
M Long

A relay used for protection of motors against overload is

  1. Impedance relay
  2. Electromagnetic attraction type
  3. Thermal relay
  4. Buchholz’s relay

Answer (Detailed Solution Below)

Option 3 : Thermal relay

Protective Relays Question 12 Detailed Solution

Download Solution PDF

Relay

Uses

Impedance relay

Phase fault and ground fault protection

Electromagnetic attraction type

Power-system protection

Thermal relay

Protection of motor against overload

Buchholz’s relay

Protection of transformer against all internal faults.

When the fault current is 2000 A, for a relay setting of 50% with CT ratio 500/5, the plug setting multiplier will be:

  1. 8
  2. 2
  3. 4
  4. 16

Answer (Detailed Solution Below)

Option 1 : 8

Protective Relays Question 13 Detailed Solution

Download Solution PDF

Concept:

Plug setting multiplier is the ratio of fault current and the product of plug setting and CT ratio.

Plug setting multiplier \(= \frac{{fault\;current}}{{plug\;setting \times CT\;ratio}}\)

Calculation:

Plug setting = relay setting × secondary CT current

= 0.5 × 5 = 2.5

CT ratio \(= \frac{{500}}{5} = 100\)

Plug setting multiplier \(= \frac{{2000}}{{2.5 \times 100}} = 8\)

Which relay is also called angle impedance relay?

  1. Impedance relay
  2. Reactance relay
  3. Mho relay
  4. Frequency relay

Answer (Detailed Solution Below)

Option 3 : Mho relay

Protective Relays Question 14 Detailed Solution

Download Solution PDF

Mho Relay:

A Mho relay measures a component of admittance |Y| ∠ θ. But its characteristic when plotted on the impedance diagram is a circle passing through the origin. It is also known as angle impedance relay.

The relay is called Mho relay because its characteristic is a straight line, when plotted on an admittance diagram.

Important Points:

  • Impedance relay is a voltage restrained overcurrent relay.
  • Reactance relay is an overcurrent relay with directional restraint.
  • Mho relay is a voltage restrained directional relay.
  • Reactance relay is suitable for the protection of a short transmission line because its operation is independent of arc resistance.
  • The relay which is selected for a long transmission line should be less affected due to power swings. Hence Mho relay is preferred.
  • Impedance relay is suitable for medium transmission lines.

Additional Information Mho Relay: Also known as a polarized distance relay or admittance relay, it is inherently directional and operates based on both the magnitude and angle of impedance. The term "Mho" is derived from the unit of admittance (the inverse of ohm), and it is characterized by a circular or oval operating characteristic on the impedance plane. The Mho relay is directionally sensitive and thus incorporates the angle of impedance in its operation, making it an angle impedance relay.

A power system with two generators is shown in the figure below. The system (generators, buses and transmission lines) is protected by six overcurrent relays R1 to R6. Assuming a mix of directional and non-directional relays at appropriate locations, the remote backup relays for R4 are F1 U.B Deepak 28.01.2020 D31

  1. R1, R2
  2. R2, R6
  3. R2, R5
  4. R1, R6

Answer (Detailed Solution Below)

Option 4 : R1, R6

Protective Relays Question 15 Detailed Solution

Download Solution PDF

Given the network is:

Gate EE 2016 paper 2 Images-Q13.1

In the given network,

R2, R4, and R5 are directional overcurrent relays. R1, R3 and R6 are non-directional overcurrent relays.

For the fault on line 2 i.e. L2, R3 and R4 must be operated. If R4 is not operated then R1 and R6 will operate.

F1 Ravi.R 07-07-21 Savita D1

Therefore, back up for Rare R1 and R6

The relay R3 is directly connected to relay R4, so that relay R3 can’t provide remote backup.

Get Free Access Now
Hot Links: teen patti master download teen patti vip teen patti lotus