What is the required plan size of a square sedimentation tank (as the primary sedimentation tank in sweage treatment), given that its effective depth is 3 m, and the flow rate is 40 MLD with admissible surface loading of 100,000 l/ m2 / day?

This question was previously asked in
ESE Civil 2015 Paper 2: Official Paper
View all UPSC IES Papers >
  1. 23.5 m × 23.5 m
  2. 30 m × 30 m 
  3. 20 m × 20 m
  4. 15 m × 15 m

Answer (Detailed Solution Below)

Option 3 : 20 m × 20 m
Free
ST 1: UPSC ESE (IES) Civil - Building Materials
20 Qs. 40 Marks 24 Mins

Detailed Solution

Download Solution PDF

Concept:

Surface Overflow Rate or Surface Loading: Surface overflow rate (SOR) is parameter that describes the settling characteristics of solids in a specific water or wastewater. It is defined as the volume of water flow per unit of time divided by the surface area (or plan area) of the settling basin.

Hence,

Calculations:

Given, discharge = 40 MLD = 40 × 106 litres/day and surface loading rate = SOR = 100,000 litre/ m2 / day.

∴ Surface or Plan area of the basin 

As the sedimentation tank is square in shape so plan dimension is 

∴ The plan dimension of the square sedimentation tank 20 m × 20 m.

Latest UPSC IES Updates

Last updated on Jun 23, 2025

-> UPSC ESE result 2025 has been released. Candidates can download the ESE prelims result PDF from here.

->  UPSC ESE admit card 2025 for the prelims exam has been released. 

-> The UPSC IES Prelims 2025 will be held on 8th June 2025.

-> The selection process includes a Prelims and a Mains Examination, followed by a Personality Test/Interview.

-> Candidates should attempt the UPSC IES mock tests to increase their efficiency. The UPSC IES previous year papers can be downloaded here.

Hot Links: teen patti refer earn teen patti online game teen patti master game teen patti real cash game