Three Phase Transformer Connections MCQ Quiz in தமிழ் - Objective Question with Answer for Three Phase Transformer Connections - இலவச PDF ஐப் பதிவிறக்கவும்
Last updated on Mar 10, 2025
Latest Three Phase Transformer Connections MCQ Objective Questions
Top Three Phase Transformer Connections MCQ Objective Questions
Three Phase Transformer Connections Question 1:
A 50 Hz, 3ϕ core type star-delta transformer has a line valtage ratio of 11,000/440 volts. The cross-section of the core is square with a circumscribing circle of 0.5 m diameter. If maximum flux density of 1.30 ωb/m2 then find the number of turns per phase on high voltage windings. Assume insulation occupies 8% of the total core area.
Answer (Detailed Solution Below) 191 - 193
Three Phase Transformer Connections Question 1 Detailed Solution
We known that diameter of the circumscribing is same as diagonal of the square.
Area of square core = l × b
\(l = b = \frac{{0.5}}{{\sqrt 2 }}\)
\(\therefore Area = {\left( {\frac{{0.5}}{{\sqrt 2 }}} \right)^2} = 0.125\;{m^2}\)
∴ Net cross section area = 0.125 × 0.92 = 0.115
E.M.F/Turn = 4.44 fBA = 4.44 × 50 × 1.3 × 0.115 = 33.19
Phase turn ratio \(= \frac{{11000}}{{\sqrt 3 }}:440\)
∴ Number of turn per phase on high voltage side \(= \frac{{11000}}{{\sqrt 3 \times 33.19}} \simeq 192\)Three Phase Transformer Connections Question 2:
The following connection of three single-phase transformer bank results in
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 2 Detailed Solution
3- phase to 6 - phase conversion:
- In certain applications like thyristors and rectifiers six-phase supply is required. Therefore it becomes necessary to convert three-phase ac supply into six-phase.
- By using three identical single-phase transformers suitably interconnected this can be achieved.
- The primary winding is connected in delta whereas its secondary winding is split into two halves.
- A greater number of phases also results in the reduction of harmonics in the alternating current.
- Thus conversion from three-phase to six-phase can be obtained by having two similar secondary windings for each of the primaries of the three-phase transformer.
- There are several methods of connecting transformers for obtaining a 3 - to - 6 phase transformation. A simple arrangement is known as a 6 phase star connection is below in figure
- In this connection, the primary is connected in a delta configuration and a 3-phase supply is given to the primary.
- The secondaries are provided with center taps, which are connected together to form the neutral of the 6 - phase side.
- Now we got six phases as shown in the above figure and the six-phase voltages are Van, Vdn, Vcn, Vfn, Ven, and Vbn.
- And the phaser diagram of six-phase voltages is shown below
Figure: 3 - phase voltage phasor diagram figure: 6 - phase voltage phaser diagram
Three Phase Transformer Connections Question 3:
There is a phase difference of______ between the corresponding phases of primary and secondary______ in a star/delta transformer.
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 3 Detailed Solution
Star-Delta transformer:
- Consider a 3-phase star-delta transformer with primary side Y connected (star connected) and secondary side with delta connected as shown below
- The polarity markings are indicated on each phase.
- The dots on the winding indicate the terminals which are positive at the same time on the undotted terminals.
- Phase on star side – A, B, C
- Phase on delta side – a, b, c
- The labeling is indicated to the diagram corresponding to +90° connections in which the positive sequences on the delta side are lead by 90° corresponding to the star side.
- Thus the line current flows through the phase and A.
- If we label delta as b → a, c → b, and a → c. There we will get standard Yd1, –30° connection
- If polarities on the delta side are also reversed, we get standard Yd11, 30° connection as shown in the figure given below.
- Thus we can get a phase difference of 30° between input and output of three-phase transformer by using a star-delta connection.
Important Points:
The phase shift in different connections of transformer are given below.
Transformer connections |
Phasor displacement angle |
∆/∆, Y/Y, ∆/Zig Zag Y |
0° (or) 180° |
∆/Y, Y/∆, Y/Zig Zag Y |
± 30° (or) 180° ± 30° |
Three Phase Transformer Connections Question 4:
Two single-phase 150 kVA, 7200 / 600 volt transformers are connected in open-delta. The maximum three-phase load that they can carry is:
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 4 Detailed Solution
Open-Delta Connection:
- An open delta connection transformer uses two single-phase transformers to provide a 3-phase supply to the load.
- An open-delta connection system is also called a V-V system.
- The Open-delta connection system is usually only used in emergency conditions, as its efficiency is low when compared to the delta-delta (Closed delta) system.
- The total load carried by an open delta system is 57.7% of the closed delta system.
The capacity of open-delta system = √3 × Rating of one transformer
= 0.577 × Rating of the closed delta system
Calculation:
Given,
Rating of one transformer = 150 kVA
The capacity of open delta system = √3 × Rating of one transformer
= √3 × 150 = 259.8 kVA
Therefore, the maximum three-phase load that they can carry is 259.8 kVA
Three Phase Transformer Connections Question 5:
If the star side of the star-delta transformer shown in the figure is excited by a negative sequence voltage, then
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 5 Detailed Solution
Three Phase Transformer Connections Question 6:
A balanced (positive sequence) three-phase AC voltage source is connected to a balanced, start connected through a star-delta transformer as shown in the figure. The line-to-line voltage rating is 230 V on the star side, and 115 V on the delta side. If the magnetizing current is neglected and \({\bar I_s} = 100\angle 0^\circ A,\) then what is the value of \({\bar I_p}\) in Ampere?
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 6 Detailed Solution
Explanation:
Given figure can be redrawn as,
With primary star (γ) side,
Phase voltage (va) = \(\rm \frac{line voltage (V_{ab})}{\sqrt{3}}=\frac{230}{\sqrt{3}}\)
At secondary delta (Δ) side,
Phase voltage (VA) = line voltage (VAB) = 115 V
Transformation ratio (k) = \(\frac{V_A}{V_a}=\frac{115}{\frac{230}{\sqrt{3}}}=0.87\)
Phase current (IA) on Δ side is,
\(I_A=\frac{I_s\rm(line)}{\sqrt{3}}=\frac{100}{\sqrt{3}}=57.7\)
∴ Is lags IA by 30°
So, IA = 57.7 ∠30°
Now, \(k=\frac{I_p}{I_A}\)
⇒ IP = k IA = 0.87 × 57.7∠30°
⇒ = 50.199 ∠30°
Hence, the correct answer is (A).
Three Phase Transformer Connections Question 7:
The distribution transformer is generally connected in -
[Δ – Delta; Y – Star]
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 7 Detailed Solution
Delta – star connection is most economical for step-up applications(transmission side) and also the secondary side (Y) connection provides a stable neutral point for 1-ϕ loads in the distribution network (3-ϕ, 4 wire).
∴ Δ - Y connection is popular for both the step-up (transmission side, high voltage) and step-down(distribution side, low voltage) applications.
- Delta-star connected distribution transformers are widely used in low power distribution for 3 phase 4 wire supply.
- The primary winding connected in delta providing a three-wire balanced load to the utility company
- While the secondary winding connected in the star connection, to provide the required 4th-wire neutral or earth connection.
Important Points
Star – delta connection is the most uneconomical among all the transformer connections because, for the same voltage rating, it requires more number of turns per phase. The economical use of this connection is connecting (Y) on HV side and (Δ) on LV side (i.e.Step-down application in transmission). But it can't be used in the distribution network due to the absence of a stable neutral point on secondary.
Star – star connection is used for high voltage and low current rating (small kVA) transformers.
Delta – delta connection is used for low voltage and high current rating (large kVA) transformers.
Three Phase Transformer Connections Question 8:
A 230/2300 V, Y/Δ 3-phase transformer is rated at 230 KVA. Its rated secondary current/phase is
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 8 Detailed Solution
Star to Delta transformer:
A star to delta transformer has a primary side as star connected and secondary is delta connected
Circuit diagram of the star to delta transformer:
Where,
IR IY IB are line currents
IRY IYB IBR are phase currents
VR VY VB are line voltages
VRY VYB VBR are phase voltages
S = √3 VL IL
Where,
IL is the line current
IP is the phase current
S is the apparent power
IL = S / √3 VL
Calculation:
Given,
Apparent power S = 230 kVA
Secondary line voltage VL = 2300 V
S = √3 VL IL
IL is the line current
IL = S / √3 VL
= (230 × 103) / (√3 × 230)
= 100 / √3 A
Phase current IP = IL / √3
= 100 / 3 = 33.33 A
∴ Its rated secondary current/phase is 33.33 A
Points to remember:
Differences between star and delta connection
Three Phase Transformer Connections Question 9:
A 3-phase star-delta transformer is used to step down the voltage of a 3-phase 11 kV feeder line. Per phase turns ratio is 12. For a primary line current of 20 A, the output kVA is _____
Answer (Detailed Solution Below) 380 - 382
Three Phase Transformer Connections Question 9 Detailed Solution
Phase voltage on primary \(\left( {{V_{p1}}} \right) = \frac{{{V_{L1}}}}{{√ 3 }} = \frac{{11 × {{10}^3}}}{{√ 3 }}V\)
Phase current on primary (Ip1) = IL1 = 20 A
Per phase turns ratio = 12
Phase voltage on secondary \(\left( {{V_{p2}}} \right) = \frac{{11 × {{10}^3}}}{{12 × √ 3 }} = 529.23\;V\)
Phase current on secondary (Ip2) = 20 × 12 = 240 A
Output kVA = 3 Vp2 Ip2 × 10-3
= 3 × 529.23 × 240 × 10-3
= 381.05 kVA
Alternate solution:
In a transformer, the power & frequency remains constant from primary to secondary
So, output power = primary side power i/p
= √3 × VL × IL
= √3 × 11 kV × 20 = 381.05 kVA
Three Phase Transformer Connections Question 10:
A delta/delta connected three-phase transformer can be connected in parallel with:
Answer (Detailed Solution Below)
Three Phase Transformer Connections Question 10 Detailed Solution
The correct answer is option "3".
Concept:-
Parallel operation of Transformer:
When two transformers operate in parallel then the input and output of the two transformers must be the same. Suppose two transformers A and B are operated in parallel then the primary of transformer A is star connected then the primary of the second transformer B should be star connected.
The transformer windings can be connected in various ways that produce magnitudes and phase displacements in the secondary voltage with respect to the primary voltage.
All the transformer connections can be classified into distinct vector groups.
Group 1: Zero phase displacement (Yy0, Dd0, Dz0)
Group 2: 180° phase displacement (Yy6, Dd6, Dz6)
Group 3: - 30° phase displacement (Yd1, Dy1, Yz1)
Group 4: + 30° phase displacement (Yd11, Dy11, Yz11)
- In order to have zero relative phase displacement of secondary-side line voltages, the transformers belonging to the same phase angle (the only magnitude not sign) to be connected in parallel.
- The transformers of groups 1 and 2 can only be paralleled with transformers of their own group.
- The transformers of groups 3 and 4 can be paralleled by reversing the phase sequence of one of them.
Transformers with Yd11 and Dy1 connections can be paralleled.
Δ-Y and Δ-Y belong to the same vector group.
Additional Information
Condition for parallel operation of transformers:
For parallel connection of transformers, primary windings of the Transformers are connected to source bus-bars and secondary windings are connected to the load bus-bars.
Various conditions that must be fulfilled for the successful parallel operation of transformers:
1. Same voltage Ratio & Turns Ratio (both primary and secondary Voltage Rating is same).
2. Same Percentage Impedance and X/R ratio.
3. Identical Position of Tap changer.
4. Same KVA ratings.
5. Same Phase angle shift (vector group is same).
6. Same Frequency rating.
7. Same Polarity.
8. Same Phase sequence.
Some of these conditions are convenient and some are mandatory.\
Important Points The convenient conditions are the Same voltage Ratio & Turn Ratio, Same Percentage Impedance, Same KVA Rating, and Same Position of Tap changer.
The mandatory conditions are the Same Phase Angle Shift, Same Polarity, Same Phase Sequence, and Same Frequency.
When the convenient conditions are not met paralleled operation is possible but not optimal.