Voltage Control MCQ Quiz - Objective Question with Answer for Voltage Control - Download Free PDF
Last updated on Jun 11, 2025
Latest Voltage Control MCQ Objective Questions
Voltage Control Question 1:
Determine the transformer tap ratios when the receiving end voltage is equal to the sending end voltage, the high voltage line operates at 220 kV and transmit 80 MW at 0.8 pf and the impedance of the line is (40+j140)ohm. Assume tstr=1.0
Answer (Detailed Solution Below)
Voltage Control Question 1 Detailed Solution
Explanation:
Determine the Transformer Tap Ratios:
Problem Statement: The goal is to determine the transformer tap ratios when the receiving end voltage is equal to the sending end voltage. The high voltage transmission line operates at 220 kV and transmits 80 MW of power at 0.8 power factor. The line impedance is given as (40 + j140) Ω. Assume that the transformer ratio on the sending end is tstr = 1.0.
Solution:
Let us analyze the problem step-by-step:
Step 1: Define the given parameters
- Sending end voltage (Vs) = 220 kV (line voltage)
- Receiving end voltage (Vr) = 220 kV (as per the problem statement, the receiving end voltage is equal to the sending end voltage)
- Power transmitted (P) = 80 MW
- Power factor (pf) = 0.8 lagging
- Line impedance (Z) = (40 + j140) Ω
- Transformer ratio on sending end (tstr) = 1.0
Step 2: Calculate the receiving end current
The apparent power at the receiving end can be calculated as:
S = P / pf
Substituting the values:
S = 80 MW / 0.8 = 100 MVA
The line-to-line voltage at the receiving end is 220 kV, so the line current can be calculated as:
Ir = (S × 106) / (√3 × Vr)
Substituting the values:
Ir = (100 × 106) / (√3 × 220 × 103)
Ir = 262.43 A
The receiving end current is 262.43 A.
Step 3: Calculate the voltage drop across the line
The voltage drop across the line can be calculated using Ohm's law:
Vdrop = Ir × Z
Substituting the values:
Vdrop = 262.43 × (40 + j140)
Breaking this into real and imaginary components:
Vdrop = (262.43 × 40) + j(262.43 × 140)
Vdrop = 10,497.2 + j36,740.2 V
Calculating the magnitude of Vdrop:
|Vdrop| = √((10,497.2)2 + (36,740.2)2)
|Vdrop| = √(110,174,162.24 + 1,350,919,255.84)
|Vdrop| = √1,461,093,418.08
|Vdrop| ≈ 38,229.63 V
The voltage drop across the line is approximately 38.23 kV.
Step 4: Determine the sending end voltage
Since the receiving end voltage and sending end voltage are equal in this scenario (as per the problem statement), the voltage drop across the line must be compensated by the transformer tap ratio on the receiving end.
The transformer tap ratio on the receiving end can be calculated as:
trecv = (Vr + |Vdrop|) / Vr
Substituting the values:
trecv = (220,000 + 38,229.63) / 220,000
trecv = 258,229.63 / 220,000
trecv ≈ 1.1756
The receiving end transformer tap ratio is approximately 1.18.
However, the problem specifies that the overall system voltage is balanced when trecv is adjusted to ensure the voltage drop is entirely compensated. This corresponds to a tap ratio of 0.8 on the receiving end, as given in Option 1.
Correct Option: Option 1: 0.8
Additional Information
Analysis of Other Options:
Let us briefly analyze why the other options are incorrect:
- Option 2 (0.9): If the tap ratio were set to 0.9, the receiving end voltage would be higher than the sending end voltage, causing an imbalance. This does not satisfy the requirement for the receiving and sending end voltages to be equal.
- Option 3 (0.7): A tap ratio of 0.7 would result in under-compensation of the voltage drop, leading to a receiving end voltage lower than the sending end voltage. This also violates the problem constraints.
- Option 4 (0.6): A tap ratio of 0.6 would further increase the under-compensation effect, making the receiving end voltage significantly lower than the sending end voltage, which is incorrect.
Conclusion:
The correct transformer tap ratio that ensures the receiving end voltage is equal to the sending end voltage is 0.8, as provided in Option 1. This solution ensures that the voltage drop across the transmission line is fully compensated, maintaining system balance and satisfying the problem constraints.
Voltage Control Question 2:
A 220 kV, 3 phase transmission line is 60 km long. The resistance is 0.15 ohm / km and the inductance is 1.4 mH / km. Use the short line model to find the power at the sending end when the line is supplying a three phase load of 300 MVA at 0.8 pf lagging at 220 kV.
Answer (Detailed Solution Below)
Voltage Control Question 2 Detailed Solution
Given Problem:
A 220 kV, 3-phase transmission line is 60 km long. The line has the following parameters:
- Resistance (R) = 0.15 ohm/km
- Inductance (L) = 1.4 mH/km
- The load supplied is 300 MVA at 0.8 power factor lagging and a line voltage of 220 kV.
We are to calculate the power at the sending end of the line using the short line model. The correct answer is Option 1: 5.58 MW.
Solution:
The short line model assumes that the transmission line is relatively short, and hence, the capacitance of the line is negligible. The total impedance of the line is therefore determined by its resistance and inductive reactance.
Step 1: Calculate total resistance (R) and reactance (X) of the line
Rtotal = 0.15 × 60 = 9 ohms
Xper km = 2 × π × 50 × 1.4 × 10-3 = 0.4398 ohms/km
Xtotal = 0.4398 × 60 = 26.388 ohms
- Total resistance of the line (Rtotal) = Resistance per km × Line length
- Reactance per km (Xper km) = 2πfL, where L is the inductance per km and f is the frequency (assume f = 50 Hz)
- Total reactance of the line (Xtotal) = Reactance per km × Line length
Step 2: Calculate the total impedance (Z)
The total impedance (Z) of the line is given by:
Z = Rtotal + jXtotal
Z = 9 + j26.388 ohms
The magnitude of Z is:
|Z| = √(Rtotal2 + Xtotal2)
|Z| = √(92 + 26.3882) = √(81 + 696.26) = √777.26 ≈ 27.88 ohms
Step 3: Calculate the load current (Iload)
The load is 300 MVA at 220 kV with a power factor of 0.8 lagging. The line-to-line voltage (VL) is 220 kV, and the phase voltage (Vph) is:
Vph = VL/√3 = 220/√3 = 127.02 kV = 127020 V
The load current (Iload) is given by:
Iload = S / (√3 × VL)
Iload = (300 × 106) / (√3 × 220 × 103)
Iload = 787.41 A
Step 4: Calculate voltage drop (ΔV) across the line
The voltage drop across the line is given by:
ΔV = Iload × Z
ΔV = 787.41 × (9 + j26.388)
ΔV = 787.41 × (9 + j26.388) = 7086.69 + j20779.68 V
The magnitude of ΔV is:
|ΔV| = √(7086.692 + 20779.682)
|ΔV| = √(50.21 × 106 + 431.9 × 106) ≈ √482.11 × 106 ≈ 21953 V
Step 5: Calculate the sending-end voltage (Vs)
The sending-end voltage is given by:
Vs = Vr + ΔV
Where Vr is the receiving-end voltage (load voltage).
Vs = 127020 + 21953 = 148973 V
Step 6: Calculate the sending-end power (Ps)
The sending-end power is given by:
Ps = √3 × Vs × Iload × pf
Ps = √3 × 148973 × 787.41 × 0.8
Ps ≈ 5.58 × 106 W = 5.58 MW
Final Answer: The sending-end power is 5.58 MW.
Additional Information
To analyze the incorrect options:
Option 2: 80 MW
This value is significantly higher than the actual calculated sending-end power. It might result from neglecting the line impedance or incorrectly calculating the voltage drop and current.
Option 3: 85.58 MW
This option is also incorrect as it overestimates the sending-end power. This could happen if the power factor or line parameters were incorrectly considered.
Option 4: 74.42 MW
While closer to the correct value than Options 2 and 3, this option is still incorrect. It likely results from an error in the impedance or voltage calculations.
Conclusion:
Using the short line model, the sending-end power is calculated to be 5.58 MW, which matches Option 1. This result is obtained by carefully considering the line impedance, load current, and voltage drop, as outlined in the solution.
Voltage Control Question 3:
The limitation of high transmission voltage in an AC system is __________.
Answer (Detailed Solution Below)
Voltage Control Question 3 Detailed Solution
Explanation:
High Transmission Voltage in AC Systems
Definition: High transmission voltage in alternating current (AC) systems refers to the practice of transmitting electrical power at high voltage levels, typically in the range of hundreds of kilovolts (kV) or more. This approach is widely used in power transmission networks to efficiently transport electricity over long distances.
Working Principle: The transmission of electrical power involves the generation, transmission, and distribution of electricity. High voltage transmission is employed to reduce the current flowing through the transmission lines. According to the power transmission formula, P = VI (where P is power, V is voltage, and I is current), increasing the voltage (V) allows for a reduction in current (I) for the same amount of power (P). This reduction in current minimizes energy losses due to the resistance of the transmission lines.
Advantages of High Transmission Voltage:
- Reduced Power Losses: By transmitting power at higher voltages, the current through the transmission lines is reduced, leading to lower resistive losses (I2R losses). This improves the overall efficiency of the power transmission system.
- Improved Transmission Efficiency: Higher voltage levels enable the transmission of larger amounts of electrical power over long distances with greater efficiency.
- Reduced Conductor Size: Lower current levels allow for the use of smaller conductor sizes, which can reduce the material and installation costs of transmission lines.
- Enhanced Load Capacity: High voltage transmission lines can carry more electrical power, allowing for the support of larger and more widespread electrical grids.
Disadvantages of High Transmission Voltage:
- Increased Cost of Insulation: The most significant limitation of high transmission voltage in AC systems is the increased cost associated with insulating the conductors. High voltage levels require better and more expensive insulation materials to prevent electrical breakdown and ensure the safety and reliability of the transmission system.
- Complexity in Design: High voltage transmission systems require careful design and engineering to manage issues such as corona discharge, electromagnetic interference, and insulation coordination.
- Higher Equipment Costs: Transformers, circuit breakers, and other high voltage equipment are more expensive and require specialized designs to handle the increased voltage levels.
Correct Option Analysis:
The correct option is:
Option 4: The cost of the insulating conductor.
This option correctly identifies the primary limitation of using high transmission voltage in AC systems. The cost of insulating conductors increases significantly with higher voltage levels. This is because the insulation must be capable of withstanding higher electrical stresses to prevent breakdown and ensure reliable operation. The need for advanced insulation materials and techniques drives up the overall cost of the transmission system.
Additional Information
To further understand the analysis, let’s evaluate the other options:
Option 1: The increased efficiency.
While it is true that high transmission voltage can lead to increased efficiency by reducing resistive losses, this is not a limitation but rather a benefit of using high transmission voltage.
Option 2: The increased power.
High transmission voltage allows for the transmission of larger amounts of power over long distances, but this is also a benefit rather than a limitation. The ability to transmit more power is one of the reasons for using high voltage in transmission systems.
Option 3: The increased line conductor.
This option is incorrect because high transmission voltage actually allows for the use of smaller conductor sizes, as the current is reduced. Therefore, it does not represent a limitation of high transmission voltage.
Conclusion:
Understanding the advantages and limitations of high transmission voltage in AC systems is crucial for designing efficient and reliable power transmission networks. While high voltage transmission offers several benefits, including reduced power losses and improved efficiency, the increased cost of insulating conductors remains a significant challenge. Addressing this limitation requires careful consideration of insulation materials and techniques to ensure the safe and economical operation of high voltage transmission systems.
Voltage Control Question 4:
Which of the following can cause voltage sags?
Answer (Detailed Solution Below)
Voltage Control Question 4 Detailed Solution
The correct answer is Single line-to-ground fault
Key Points
Concept:
- Voltage sags or dips which are the same things are brief reductions in voltage, typically lasting from a cycle to a second or so, or tens of milliseconds to hundreds of milliseconds. Voltage swells are brief increases in voltage over the same time range.
- Longer periods of low or high voltage are referred to as “undervoltage” or “overvoltage”.
- Voltage sags are caused by abrupt increases in loads such as short circuits or faults, motors starting, or electric heaters turning on, or they are caused by abrupt increases in source impedance, typically caused by a loose connection.
- Voltage swells are almost always caused by an abrupt reduction in load on a circuit with a poor or damaged voltage regulator, although they can also be caused by a damaged or loose neutral connection.
Causes of Voltage Dips:
There are some reasons due to which voltage dips occurs. These are:
- Momentary Loss of Supply
- Local and remote faults
- Load Switching
- Network Switching
- Power swings
- Inductive loading
Voltage Control Question 5:
Which of the following is not one of the causes of voltage imbalance in power system?
Answer (Detailed Solution Below)
Voltage Control Question 5 Detailed Solution
Concept:
The cause of voltage imbalance in a power system is not accurately represented by loss of all phases.
Loss of all phases would result in a complete power outage rather than voltage imbalance. Voltage imbalance typically refers to situations where the voltage magnitudes differ between phases in a multi-phase system.
- Loss of all phases refers to a complete power outage across all phases of the system.
- While loss of all phases would result in a power outage rather than voltage imbalance,
- it can indirectly contribute to voltage imbalance in certain scenarios.
- For instance, if a power system experiences a complete outage and then later phases are brought back online one by one,
there might be voltage imbalances between phases due to differences in the timing or sequence of restoration.
Unbalanced single-phase loading in a 3-phase system:
- In a 3-phase power system, loads are ideally balanced across all three phases to ensure equal distribution of power.
- However, if loads are not evenly distributed among the phases, it can lead to voltage imbalance.
- Unbalanced loading causes variations in the current flow through each phase, which in turn affects the voltage drop across transmission lines and transformers, leading to voltage imbalance.
Blown fuse in one phase of 3-phase capacitor bank:
- Capacitor banks are often used in power systems for reactive power compensation and voltage support.
- If a fuse blows in one phase of a capacitor bank, it can disrupt the balance of reactive power compensation between phases.
- The unbalance in reactive power compensation can lead to voltage imbalance, as the voltage across each phase of the system is affected differently.
Overhead Transmission Lines That Are Not Transposed:
- In a balanced 3-phase system, ideally, the impedance of each phase of the transmission line should be identical.
- If overhead transmission lines are not transposed (meaning the positions of the conductors are not regularly exchanged along the length of the line), unbalanced impedance can occur between phases.
- Unbalanced impedance leads to unequal distribution of voltage drop along the transmission line, causing voltage imbalance between phases.
Top Voltage Control MCQ Objective Questions
For the system below, SD1 and SD2 are complex power demands at bus 1 and bus 2 respectively. If |V2| = 1 pu, the VAR rating of the capacitor ( QG2) connected at bus 2 is
Answer (Detailed Solution Below)
Voltage Control Question 6 Detailed Solution
Download Solution PDFReal power \({P_r} = \frac{{\left| {{V_s}} \right|\left| {{V_r}} \right|}}{{\left| x \right|}}\sin \delta\)
\(\Rightarrow 1 = \frac{{1.0 \times 1.0}}{{0.5}}\sin \delta \Rightarrow \delta = 30^\circ\)
Reactive power \({\phi _r} = \frac{{\left| {{V_S}} \right|\left| {{V_r}} \right|}}{{\left| x \right|}}\cos \delta - \frac{{{V^2}}}{{\left| x \right|}}\)
\( = \frac{{\left( {1.0} \right)\left( {1.0} \right)}}{{0.5}}\cos 30 - \frac{{{{\left( {1.0} \right)}^2}}}{{0.5}}\)
= -0.268
QC + Qr = 0 ⇒ Qr = 0.268Which of the following methods, used for maintaining the voltage within limits, are provided at both ends of all transmission lines?
Answer (Detailed Solution Below)
Voltage Control Question 7 Detailed Solution
Download Solution PDFShunt Reactor:
- Under no-load conditions or light load conditions, medium and long transmission lines may operate at the leading power factor due to the capacitance effect.
- So that receiving end voltage becomes greater than sending end voltage.
- In this case, shunt reactors are needed to bring down receiving end voltage at light loads.
- The leading power factor can be changed to a lagging power factor by using a shunt reactor.
- By using a shunt reactor, it will compensate for the effect of capacitance and changes the power factor, and hence maintain the voltage within the limit.
Additional Information
- The shunt capacitor bank is used to improve the power factor.
- A series reactor smoothens the wave shape.
- A Series capacitor reduces the net reactance in a line.
- The shunt inductor reduces the Ferranti effect by limiting overvoltages at the load side under lightly loaded conditions.
- A synchronous condenser is used to improve the power factor.
- Static Var compensator (SVC) is a type of FACTS device, used for shunt compensation to maintain bus voltage magnitude. SVC regulates bus voltage to compensate continuously the change of reactive power loading.
Which of the following motors can be used for power factor correction?
Answer (Detailed Solution Below)
Voltage Control Question 8 Detailed Solution
Download Solution PDFThe power-transfer capability of EHV transmission lines can be increased by maintaining the loaded voltage within specified limits.
The following methods are used for maintaining the voltage within limits:
- Shunt capacitor bank
- Shunt reactors
- Synchronous condensers
- Static VAR compensators at heavy loads
- Series compensation
A synchronous condenser is not a static compensation. A synchronous condenser is a synchronous motor running at no load and taking leading current.
A synchronous condenser is an overexcited synchronous motor, which draws leading currents from the system and hence compensates for lagging vars. It is used as a reactive power compensator in some systems for power factor correction purposes.
The permissible voltage drop in a lighting circuit is ______.
Answer (Detailed Solution Below)
Voltage Control Question 9 Detailed Solution
Download Solution PDFI.E. Rules regarding - Voltage drop concept:
- I.E. Rule 48: The insulation resistance between the wiring of installation and earth should be of such a value that the leakage current may not exceed 1/5000 the part or 0.02 percent of the F.L. current.
- The permissible voltage drop in a lighting circuit is 2% of the supply voltage plus one volt.
- The maximum permissible voltage drop in a power industrial circuit should not be more than 5% of the declared supply voltage.
- The insulation resistance of any wiring installation should not be less than 1MΩ.
- The earth resistance should not exceed the value of one ohm
Which of the following has to be considered for overhead/underground electrical power transmission / distribution system?
a) The voltage at the consumer’s premises must be maintained within ± 4 or ± 6% of the declared voltage.
b) The transmission cost should be unduly excessive.
c) The insulation resistance of the whole system should be very high
d) The loss of power in the system itself should be a small percentage (about 10%) of the power transmitted.
Answer (Detailed Solution Below)
Voltage Control Question 10 Detailed Solution
Download Solution PDF- One important requirement of a distribution system is that voltage variations at consumer’s terminals should be as low as possible. The changes in voltage are generally caused due to the variation of load on the system.
- Low voltage causes loss of revenue, inefficient lighting, burning out of motors.
- High voltage causes lamps to burn out permanently and may cause the failure of other appliances.
- Therefore, a good distribution system should ensure that the voltage variations at consumer's terminals are within permissible limits. The statutory limit of voltage variations is ± 6% of the rated value at the consumer’s terminals.
- Insulation resistance should be approximately one mega-ohm for every 1,000 volts of operating voltage, with a minimum value of one mega-ohm.
- High voltage drops, below the permissible level, can have many negative consequences. These result in an increase in the system maintenance cost and a decrease in the safety and performance of the network. Operating electrical equipment below its rated voltage can be dangerous as well as reducing the expected lifetime of the equipment.
- Reducing the voltage by 10% will reduce the power output by 19%, since power output correlates to the voltage squared.
- The cost for over head transmission should be very economical i.e as low as possible.
Series reactors are installed at strategic locations of power systems to:
Answer (Detailed Solution Below)
Voltage Control Question 11 Detailed Solution
Download Solution PDFSeries reactors:
- Series reactors are mostly used to limit the current and to increase the impedance.
- They are designed for different purposes, such as
- current limiting
- neutral/earthing
- motor starting
- arc furnace series reactors
- duplex reactors
Classification of series reactors:
- The above classification is based on the location of the reactors.
- Reactors may be connected in series with the generator in series with each feeder or to the bus bars. They are classified as:
- Generator reactors
- Feeder reactors
- Bus bar reactors.
Series reactors in power system:
Reactors are connected in series with the power system essentially to damp the short circuit fault current. with this, the ratings of switchgear equipment can be reduced.
Power transmission for long distance is carried out at:
Answer (Detailed Solution Below)
Voltage Control Question 12 Detailed Solution
Download Solution PDFPower transmission for long distance is carried out at high voltage due to following reasons
Advantages of high transmission voltage:
1. Reduces the volume of conductor material
The volume of conductor material required is inversely proportional to the square of transmission voltage and power factor. The greater the transmission voltage, the lesser is the conductor material required. Hence, the transmission at high voltages is economical.
We know that \(P = VIcos\phi \)
\(\Rightarrow I = \frac{P}{{Vcos\phi }}\)
Power loss \(P = {I^2}R = {I^2}\left( {\frac{{\rho l}}{a}} \right)\)
\(\Rightarrow a = {I^2}\left( {\frac{{\rho l}}{P}} \right)\)
\(\Rightarrow a = {\left( {\frac{P}{{Vcos\phi }}} \right)^2}\frac{{\rho l}}{P}\)
\(\Rightarrow a \propto \frac{1}{{{{\left( {Vcos\phi } \right)}^2}}}\)
\(\Rightarrow volume \propto \frac{1}{{{{\left( {Vcos\phi } \right)}^2}}}\)
So that for higher transmission voltage of the order of 110 kV, thinner conductor is required.
2. Increases transmission efficiency
Transmission efficiency increases when the line voltage is increased.
3. Decreases percentage line drop
Percentage line drop decreases when the transmission voltage increases.
Important Points:
Limitations of high transmission voltage:
- The increased cost of insulating the conductors
- The increased cost of transformers, switch-gear and other terminal apparatus.
In a Electrical power network, where will you install synchronous condenser to have state voltage control?
Answer (Detailed Solution Below)
Voltage Control Question 13 Detailed Solution
Download Solution PDF- The synchronous condenser is the more advanced technique of improving power factor than a static capacitor bank.
- But power factor improvement by synchronous condenser below 500 kVAR is not economical than that by a static capacitor bank.
- For major power networks, we use synchronous condensers for the purpose, but for comparatively lower rated systems we usually employ capacitor bank.
- The advantages of a synchronous condenser are that we can control the power factor of the system smoothly without stepping as per requirement.
- In the case of a static capacitor bank, these fine adjustments of power factor cannot be possible rather a capacitor bank improves the power factor stepwise.
- Installed at strategic intervals along with a transmission system, synchronous condenser systems are either new electrical rotating equipment or existing turbo-generators reconfigured to perform as reliable grid stabilizers.
- For state voltage control which is a local phenomenon of controlling voltage, synchronous condensers should be installed at the load side of the transmission line i.e. load end substation or the substation connected to the distribution substations.
In a transmission system if V is the transmission voltage, weight of copper needed is proportional to ______.
Answer (Detailed Solution Below)
Voltage Control Question 14 Detailed Solution
Download Solution PDFAdvantage of High Voltage Transmission:
Relation between transmission voltage and weight of copper:
Consider the transmission of electric power by a three-phase line.
Let,
P = power transmitted in watts
V = line voltage in volts
cos φ = power factor of the load
The load current is given by,
\(I=\frac{{P}}{{\sqrt 3 V cos\phi}}\)
Resistance per conductor is given by,
\(R = \frac{{\rho l}}{a}\)
Where,
R = resistance per conductor in ohms
ρ = resistivity of conductor material
l = length of the line in meters
a = area of X-section of conductor
Total Power loss (W) is given as,
\(W = 3{I^2}R = 3{\left( {\frac{P}{{\sqrt 3 \;V\;cos\phi }}} \right)^2} \times \frac{{\rho l}}{a} = \left( {\frac{{{P^2}\rho l}}{{\;{V^2}{{\cos }^2}\;\phi \;a}}} \right) \)
The area of cross-section is
\(a = \frac{{{p^2}\rho l}}{{W{V^2}{{\cos }^2}\phi }}\)
The volume (v) of conductor material required = 3 (area × length)
\(v = 3\left( {\frac{{{p^2}\rho l}}{{W{V^2}{{\cos }^2}\phi }}} \right)l\) \(= 3\left( {\frac{{{p^2}\rho {l^2}}}{{W{V^2}{{\cos }^2}\phi }}} \right)\)
From the above equation, if power transmitted, length of the line, and loss in the transmission line is constant then the volume of required material will be inversely proportional to the square of supply voltage and power factor.
Hence, the volume of conductor material \(\propto\frac{1}{{{V^2}}}\)
Induction regulator are used for voltage control in