Measurement of 3 Phase Reactive Power Using 2 Wattmeters MCQ Quiz - Objective Question with Answer for Measurement of 3 Phase Reactive Power Using 2 Wattmeters - Download Free PDF
Last updated on Mar 20, 2025
Latest Measurement of 3 Phase Reactive Power Using 2 Wattmeters MCQ Objective Questions
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 1:
Two wattmeters are connected to measure power in a three-phase system. Reading of one of the wattmeter is zero. Then power factor of the three-phase load is:
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 1 Detailed Solution
Explanation:
In a three-phase system, power measurement using two wattmeters is a common method known as the two-wattmeter method. This method is widely used for measuring power in both balanced and unbalanced three-phase systems. To understand the situation where one of the wattmeters reads zero, we need to delve into the principles of this method and the relationship between the readings and the power factor of the load.
Two-Wattmeter Method:
The two-wattmeter method involves connecting two wattmeters to a three-phase system to measure power. The readings of the two wattmeters (W1 and W2) can be used to determine the total power (P) and the power factor (pf) of the system. The total power is given by the sum of the readings:
P = W1 + W2
The power factor can be determined using the difference between the readings:
pf = cos(Φ) = (W1 - W2) / (W1 + W2)
Where Φ is the phase angle between the line voltage and the line current.
Scenario Analysis:
In the scenario where one of the wattmeters reads zero, let's assume that W1 = 0. This means that the entire power is being measured by the second wattmeter (W2). Therefore, the total power (P) is:
P = W1 + W2 = 0 + W2 = W2
Now, using the formula for power factor:
pf = cos(Φ) = (W1 - W2) / (W1 + W2) = (0 - W2) / (0 + W2) = -W2 / W2 = -1
However, the power factor cannot be -1 because it represents a purely inductive load, which is not possible in this context. Therefore, we need to consider the magnitude of the power factor:
|pf| = |cos(Φ)| = |-1| = 1
This represents a power factor of unity, which means the load is purely resistive. However, this is a theoretical consideration. Practically, the power factor can be determined by the specific configuration of the load and the readings of the wattmeters.
In a balanced three-phase system, if one of the wattmeters reads zero, it indicates that the load has a power factor of 0.5. This situation arises because the angle between the voltage and the current is 60 degrees (cos(60) = 0.5). Therefore, the correct power factor in this scenario is:
Correct Option: 0.5
The correct answer is option 3, which indicates that the power factor of the three-phase load is 0.5.
Additional Information
To further understand the analysis, let’s evaluate the other options:
Option 1: Zero
If the power factor were zero, it would imply that the load is purely reactive (either inductive or capacitive), and no real power is being consumed. This would mean that both wattmeters should read zero, which is not the case here.
Option 2: Unity
A unity power factor (pf = 1) indicates a purely resistive load where the voltage and current are in phase. In such a case, both wattmeters would have equal readings, and neither would read zero. Therefore, this option is incorrect.
Option 4: 0.707
This value corresponds to a power factor angle of 45 degrees (cos(45) = 0.707). For this power factor, the readings of the two wattmeters would be different but not zero. Therefore, this option is incorrect.
Conclusion:
Understanding the two-wattmeter method and the relationship between the wattmeter readings and the power factor is crucial for accurately determining the power factor of a three-phase load. In this case, when one of the wattmeters reads zero, the power factor of the load is 0.5, which corresponds to an angle of 60 degrees between the voltage and the current. This analysis helps in correctly identifying the operating conditions of the three-phase system.
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 2:
Two wattmeter method is used to measure the power in a 3-phase system. When both meters are normally phased, the meter readings are 2400 W and 1260 W. What is the load power?
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 2 Detailed Solution
Two Wattmeter Method of Power Measurement
The Wattmeter Method can be employed to measure the power in a 3 phase, three-wire star, or delta connected or balanced or unbalanced load.
In the wattmeter method, the current coils of the wattmeter are connected with any two lines, say R and Y, and the potential coil of each wattmeter is joined on the same line, the third line i.e. B as shown in below figure.
The wattmeter meter readings are:
\(W_1=V_LI_Lcos(30-\phi)\)
\(W_2=V_LI_Lcos(30+\phi)\)
where, \(\phi=tan^{-1}({\sqrt{3}(W_1-W_2)\over W_1+W_2})\)
Calculation
Given, W1 = 2400W
W2 = 1260 W
W = W1 + W2
W = 2400 + 1260
W = 3660 W
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 3:
Power is measured in a three - phase load by two - wattmeter method. The reading of one - wattmeter is 5000 W and the other wattmeter deflects in reverse direction. On interchanging the potential terminals, the second wattmeter reads 1000 W. The total power consumed by the load is
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 3 Detailed Solution
Concept:
In a two-wattmeter method, for lagging load
The reading of first wattmeter (W1) = VL IL cos (30 + ϕ)
The reading of second wattmeter (W2) = VL IL cos (30 - ϕ)
Total power in the circuit (P) = W1 + W2
Total reactive power in the circuit \(Q=\sqrt{3}\left( {{W}_{1}}-{{W}_{2}} \right)\)
Power factor = cos ϕ
\(\phi =\text{ta}{{\text{n}}^{-1}}\left( \frac{\sqrt{3}\left( {{W}_{1}}-{{W}_{2}} \right)}{{{W}_{1}}+{{W}_{2}}} \right)\)
Explanation:
In the two-wattmeter method:
- If one wattmeter shows a negative reading, it means the power factor of the load is less than 0.5.
- When the potential terminals of the second wattmeter are interchanged, it shows a positive value, giving the correct magnitude of the power it measures.
Calculation:
The total Power in a three-phase load using two wattmeter method is: Ptotal = W1 + W2
Where: W1 = 5000 W, W2 = 1000 W (after correcting the reverse deflection by interchanging potential terminals)
Ptotal = 5000 + 1000 = 6000 W
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 4:
A 300 V, 5 A, LPF wattmeter has a full scale of 300 W. The wattmeter can be used for loads supplied by 300 V ac mains with a maximum power factor of ___________ (rounded off to one decimal place).
Answer (Detailed Solution Below) 0.2
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 4 Detailed Solution
Concept:
Power measured by 1- ϕ wattmeter is given by P = VpcIcc cos ϕ
Where
Vpc = Voltage of potential coil
Icc = Current through the current coil
Application:
Here, Vpc = 300 V , Icc = 5 A , P = 300 W (Full Scale)
300 = Vpc Icc cos ϕ
300 = 300 x 5 cos ϕ
cos ϕ = 0.2
Important Points
Dynamometer type wattmeter gives more error compared to LPF wattmeter for measuring low power factor. So, the LPF wattmeter is used here for better accuracy.
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 5:
The apparent power drawn by an AC system is 50 kVA, reading of wattmeter is 20 kW. Reactive power consumed will be
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 5 Detailed Solution
Concept:
The power triangle is as shown below.
P = Active power (or) Real power in W = Vrms Irms cos ϕ
Q = Reactive power in VAR = Vrms Irms sin ϕ
S = Apparent power in VA = Vrms Irms
S = P + jQ
\(S = \sqrt {{P^2} + {Q^2}}\)
ϕ is the phase difference between the voltage and current
Power factor \(\cos \phi = \frac{P}{S}\)
Calculation:
Given that,
Apparent power (S) = 50 kVA
Reading of wattmeter = Active power (P) = 20 kW
\( \Rightarrow 50 = \sqrt {{{20}^2} + {Q^2}} \)
⇒ Q = 45.82 kVARTop Measurement of 3 Phase Reactive Power Using 2 Wattmeters MCQ Objective Questions
Two wattmeter method is used for measurement of power in a balanced three-phase load supplied from a balanced three-phase system. If one of the wattmeters reads half of the other (both positive), then the power factor of the load is
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 6 Detailed Solution
Download Solution PDFConcept:
In a two-wattmeter method, for lagging load
The reading of first wattmeter (W1) = VL IL cos (30 + ϕ)
The reading of second wattmeter (W2) = VL IL cos (30 - ϕ)
\(\phi = {\rm{ta}}{{\rm{n}}^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
Calculation:
Given that,
\({W_2} = \frac{{{W_1}}}{2}\)
We know that,
\(\phi = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
\( = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - \frac{{{W_1}}}{2}} \right)}}{{\left( {{W_1} + \frac{{{W_1}}}{2}} \right)}}} \right)\)
\(= {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {2{W_1} - {W_1}} \right)}}{{2{W_1} + {W_1}}}} \right)\)
\(= {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 {W_1}}}{{3{W_1}}}} \right) = {\tan ^{ - 1}}\left( {\frac{1}{{\sqrt 3 }}} \right) = 30^\circ \)
Power factor, cos ϕ = cos 30° = 0.866Two wattmeter method is used to measure the power in a 3-phase system. When both meters are normally phased, the meter readings are 2400 W and 1260 W. What is the load power?
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 7 Detailed Solution
Download Solution PDFTwo Wattmeter Method of Power Measurement
The Wattmeter Method can be employed to measure the power in a 3 phase, three-wire star, or delta connected or balanced or unbalanced load.
In the wattmeter method, the current coils of the wattmeter are connected with any two lines, say R and Y, and the potential coil of each wattmeter is joined on the same line, the third line i.e. B as shown in below figure.
The wattmeter meter readings are:
\(W_1=V_LI_Lcos(30-\phi)\)
\(W_2=V_LI_Lcos(30+\phi)\)
where, \(\phi=tan^{-1}({\sqrt{3}(W_1-W_2)\over W_1+W_2})\)
Calculation
Given, W1 = 2400W
W2 = 1260 W
W = W1 + W2
W = 2400 + 1260
W = 3660 W
In case of power measurements by two wattmeter method in a balanced 3 – phase system with pure inductive load
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 8 Detailed Solution
Download Solution PDFGiven that load is pure inductive – Hence it is zero power factor (lag)
Cos ϕ = 0
⇒ ϕ = 90°
We know that,
\(\begin{array}{l} \phi = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\\ \Rightarrow 90^\circ = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\\ \Rightarrow \frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}} = \tan 90^\circ = \infty \end{array}\)
⇒ W1 + W2 = 0
⇒ W1 = -W2A 300 V, 5 A, LPF wattmeter has a full scale of 300 W. The wattmeter can be used for loads supplied by 300 V ac mains with a maximum power factor of ___________ (rounded off to one decimal place).
Answer (Detailed Solution Below) 0.2
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 9 Detailed Solution
Download Solution PDFConcept:
Power measured by 1- ϕ wattmeter is given by P = VpcIcc cos ϕ
Where
Vpc = Voltage of potential coil
Icc = Current through the current coil
Application:
Here, Vpc = 300 V , Icc = 5 A , P = 300 W (Full Scale)
300 = Vpc Icc cos ϕ
300 = 300 x 5 cos ϕ
cos ϕ = 0.2
Important Points
Dynamometer type wattmeter gives more error compared to LPF wattmeter for measuring low power factor. So, the LPF wattmeter is used here for better accuracy.
Two wattmeters are connected to measure power in a three-phase system. Reading of one of the wattmeter is zero. Then power factor of the three-phase load is:
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 10 Detailed Solution
Download Solution PDFExplanation:
In a three-phase system, power measurement using two wattmeters is a common method known as the two-wattmeter method. This method is widely used for measuring power in both balanced and unbalanced three-phase systems. To understand the situation where one of the wattmeters reads zero, we need to delve into the principles of this method and the relationship between the readings and the power factor of the load.
Two-Wattmeter Method:
The two-wattmeter method involves connecting two wattmeters to a three-phase system to measure power. The readings of the two wattmeters (W1 and W2) can be used to determine the total power (P) and the power factor (pf) of the system. The total power is given by the sum of the readings:
P = W1 + W2
The power factor can be determined using the difference between the readings:
pf = cos(Φ) = (W1 - W2) / (W1 + W2)
Where Φ is the phase angle between the line voltage and the line current.
Scenario Analysis:
In the scenario where one of the wattmeters reads zero, let's assume that W1 = 0. This means that the entire power is being measured by the second wattmeter (W2). Therefore, the total power (P) is:
P = W1 + W2 = 0 + W2 = W2
Now, using the formula for power factor:
pf = cos(Φ) = (W1 - W2) / (W1 + W2) = (0 - W2) / (0 + W2) = -W2 / W2 = -1
However, the power factor cannot be -1 because it represents a purely inductive load, which is not possible in this context. Therefore, we need to consider the magnitude of the power factor:
|pf| = |cos(Φ)| = |-1| = 1
This represents a power factor of unity, which means the load is purely resistive. However, this is a theoretical consideration. Practically, the power factor can be determined by the specific configuration of the load and the readings of the wattmeters.
In a balanced three-phase system, if one of the wattmeters reads zero, it indicates that the load has a power factor of 0.5. This situation arises because the angle between the voltage and the current is 60 degrees (cos(60) = 0.5). Therefore, the correct power factor in this scenario is:
Correct Option: 0.5
The correct answer is option 3, which indicates that the power factor of the three-phase load is 0.5.
Additional Information
To further understand the analysis, let’s evaluate the other options:
Option 1: Zero
If the power factor were zero, it would imply that the load is purely reactive (either inductive or capacitive), and no real power is being consumed. This would mean that both wattmeters should read zero, which is not the case here.
Option 2: Unity
A unity power factor (pf = 1) indicates a purely resistive load where the voltage and current are in phase. In such a case, both wattmeters would have equal readings, and neither would read zero. Therefore, this option is incorrect.
Option 4: 0.707
This value corresponds to a power factor angle of 45 degrees (cos(45) = 0.707). For this power factor, the readings of the two wattmeters would be different but not zero. Therefore, this option is incorrect.
Conclusion:
Understanding the two-wattmeter method and the relationship between the wattmeter readings and the power factor is crucial for accurately determining the power factor of a three-phase load. In this case, when one of the wattmeters reads zero, the power factor of the load is 0.5, which corresponds to an angle of 60 degrees between the voltage and the current. This analysis helps in correctly identifying the operating conditions of the three-phase system.
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 11:
Two wattmeter method is used for measurement of power in a balanced three-phase load supplied from a balanced three-phase system. If one of the wattmeters reads half of the other (both positive), then the power factor of the load is
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 11 Detailed Solution
Concept:
In a two-wattmeter method, for lagging load
The reading of first wattmeter (W1) = VL IL cos (30 + ϕ)
The reading of second wattmeter (W2) = VL IL cos (30 - ϕ)
\(\phi = {\rm{ta}}{{\rm{n}}^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
Calculation:
Given that,
\({W_2} = \frac{{{W_1}}}{2}\)
We know that,
\(\phi = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
\( = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - \frac{{{W_1}}}{2}} \right)}}{{\left( {{W_1} + \frac{{{W_1}}}{2}} \right)}}} \right)\)
\(= {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {2{W_1} - {W_1}} \right)}}{{2{W_1} + {W_1}}}} \right)\)
\(= {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 {W_1}}}{{3{W_1}}}} \right) = {\tan ^{ - 1}}\left( {\frac{1}{{\sqrt 3 }}} \right) = 30^\circ \)
Power factor, cos ϕ = cos 30° = 0.866Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 12:
The apparent power drawn by an AC system is 50 kVA, reading of wattmeter is 20 kW. Reactive power consumed will be
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 12 Detailed Solution
Concept:
The power triangle is as shown below.
P = Active power (or) Real power in W = Vrms Irms cos ϕ
Q = Reactive power in VAR = Vrms Irms sin ϕ
S = Apparent power in VA = Vrms Irms
S = P + jQ
\(S = \sqrt {{P^2} + {Q^2}}\)
ϕ is the phase difference between the voltage and current
Power factor \(\cos \phi = \frac{P}{S}\)
Calculation:
Given that,
Apparent power (S) = 50 kVA
Reading of wattmeter = Active power (P) = 20 kW
\( \Rightarrow 50 = \sqrt {{{20}^2} + {Q^2}} \)
⇒ Q = 45.82 kVARMeasurement of 3 Phase Reactive Power Using 2 Wattmeters Question 13:
A 3 phase 500 V motor load has a power factor of 0.5. Two wattmeter’s connected to measure the input. They show the input to be 36 kW. The readings of both the instruments are.
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 13 Detailed Solution
Concept:
In a two-wattmeter method, for lagging load
The reading of first wattmeter (W1) = VL IL cos (30 + ϕ)
The reading of second wattmeter (W2) = VL IL cos (30 - ϕ)
Total power in the circuit (P) = W1 + W2
Total reactive power in the circuit \(Q = \sqrt 3 \left( {{W_1} - {W_2}} \right)\)
Power factor = cos ϕ
\(\phi = {\rm{ta}}{{\rm{n}}^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{{W_1} + {W_2}}}} \right)\)
Calculation:
Given that, line voltage (VL) = 500 V
Cos ϕ = 0.5
Cos ϕ = 0.5 ⇒ ϕ = 60°
W1 + W2 = 36 kW
\(\tan \phi = \frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{\left( {{W_1} + {W_2}} \right)}}\)
\(\Rightarrow \tan 60 = \frac{{\sqrt 3 \left( {{W_1} - {W_2}} \right)}}{{\left( {{W_1} + {W_2}} \right)}}\)
⇒ W1 – W2 = 36
⇒ W1 = 36 kW, W2 = 0 kWMeasurement of 3 Phase Reactive Power Using 2 Wattmeters Question 14:
Two wattmeters are connected to measure the power consumed by a 3-ϕ load with a power factor of 0.4. The total power consumed by the load as indicated by the two wattmeters is 30 kW. The difference between the two wattmeter readings is _____ kW
Answer (Detailed Solution Below) 39 - 40
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 14 Detailed Solution
Concept:
In a two-wattmeter method,
Total power (P) = P1 + P2
The power factor of the system = cos ϕ
\(\tan \phi = \sqrt 3 \frac{{[{P_1} - {P_2}]}}{{\left[ {{P_1} + {P_2}} \right]}}\)
Where P1 & P2 are power of wattmeters
Calculation:
P = 30 W, cos ϕ = 0.4
If P1 and P2 are two individual wattmeter readings then according to the problem,
P = P1 + P2 = 30 kW
Power factor angle ϕ = cos-1 (0.4) = 66.4°
So, \(\phi = {\tan ^{ - 1}}\left( {\sqrt 3 \frac{{\left( {{P_1} - {P_2}} \right)}}{{\left( {{P_1} + {P_2}} \right)}}} \right)\)
\(66.4^\circ = {\tan ^{ - 1}}\left( {\frac{{\sqrt 3 \left( {{P_1} - {P_2}} \right)}}{{30}}} \right)\)
\(\frac{{2.288\; \times \;30}}{{\sqrt 3 }} = {P_1} - {P_2}\)
39.69 kW = P1 – P2
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 15:
Two wattmeter method is used to measure the power in a 3-phase system. When both meters are normally phased, the meter readings are 2400 W and 1260 W. What is the load power?
Answer (Detailed Solution Below)
Measurement of 3 Phase Reactive Power Using 2 Wattmeters Question 15 Detailed Solution
Two Wattmeter Method of Power Measurement
The Wattmeter Method can be employed to measure the power in a 3 phase, three-wire star, or delta connected or balanced or unbalanced load.
In the wattmeter method, the current coils of the wattmeter are connected with any two lines, say R and Y, and the potential coil of each wattmeter is joined on the same line, the third line i.e. B as shown in below figure.
The wattmeter meter readings are:
\(W_1=V_LI_Lcos(30-\phi)\)
\(W_2=V_LI_Lcos(30+\phi)\)
where, \(\phi=tan^{-1}({\sqrt{3}(W_1-W_2)\over W_1+W_2})\)
Calculation
Given, W1 = 2400W
W2 = 1260 W
W = W1 + W2
W = 2400 + 1260
W = 3660 W